Corporate
Activities

Transformer Oil Filtration & Re-Generation

We specialize in oil filtration and regeneration services for all types of transformers. We also provide comprehensive Operation & Maintenance (O&M) services for both dry-type and oil-filled transformers under long-term service contracts.

Transformer Oil Filtration & Re-Generation

On-site transformer oil filtration rig connected to a power transformer in Qatar

Filtration and regeneration that brings degraded insulating oil back into specification, without replacing the full oil charge and without moving the transformer.

Six-monthly oil testing

Insulating oil should be tested every six months. A full screen covers interfacial tension, dissolved gas, flash point, sludge content, acidity, water content and dielectric strength, and the results together tell you whether the oil is still fit, needs filtration, or has gone far enough that regeneration is the only option.

When oil needs treatment

  • Dielectric strength has dropped below specification
  • Water content rising
  • Acidity climbing or interfacial tension falling
  • Sludge forming in the tank or on the windings
  • Flash point falling
  • Dissolved gas analysis showing a degradation trend

Filtration

  • On-site sampling and pre-treatment testing
  • Vacuum dehydration and degassing
  • Particulate filtration
  • Hot oil circulation
  • Post-treatment testing and a treatment record

Regeneration

  • Treatment of aged transformer oil where filtration alone is insufficient
  • Removal of acids, sludge precursors and other oil ageing products
  • Reduction in acidity and improvement in interfacial tension and oil colour
  • Extension of usable oil life where its condition allows regeneration
  • Reduced need for complete oil replacement, helping minimise associated costs, downtime and waste disposal